Vacuum Circuit Breaker

HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially for location where requires the frequent operation of rated working current or multi breaking short circuit current.
The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism.

222
NO. Item Unit Parameter
1 Rated voltage KV 12
2 Rate voltage Hz 50
3 Rated lightning impulse withstand voltage(1min) KV 75
4 Rated short-time power frequency withstand voltage (1min) KV 42
5 Rated short-circuit breaking current KA 20 25 31.5 40
6 Rated current A 630 1000
1250
630 1000
1250 1600
1250 1600
2000 2500
1600 2000
2500 3150
7 Rated peak withstand current KA 50 63 80 100
8 Rated shorted-time withstand current KA 20 25 31.5 40
9 Rated shorted-time making current(peak) KA 50 63 80 100
10 Power frequency withstand voltage of secondary circuit(1min) V 2000
11 Rated operation sequence Off-0.3s-On&Off-180s- On& Off
Off -180s- On& Off -180s- On& Off*
12 Rated breaking current of capacitor bank A 630/400(40kA 800/400)
13 Opening time(rated voltage) ms 20~50
14 Closing time(rated voltage) ms 30~70
15 Rated short-circuit current breaking times times 50(40kA 30)
16 Mechanical life times 30000
17 Rated opening/closing voltage V AC110, 220; DC110, 220
18 Rated voltage of energy-storage motor V AC110, 220; DC100, 220
222-1

3.1 Environment temperature:-15℃~+40℃;
3.2 Environment humidity: Daily average relative humidity:≤95%, monthly average relative humidity:≤90%; Daily average saturated vapor pressure:≤2.2×10-3Mpa,monthly average saturated vapor pressure:≤1.8×10-3Mpa;
3.3 Altitude: Not exceed 1000m;
3.4 Earthquake intensity: Not exceed&degree;
3.5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.